Manual Generac QT08054KNANA Generator

Need a manual for your Generac QT08054KNANA Generator? Below you can view and download the PDF manual for free in English. This product currently has 0 frequently asked questions, 0 comments and has 0 votes. If this is not the manual you want, please contact us.

Is your product defective and the manual offers no solution? Go to a Repair Café for free repair services.

Manual

Loading…

Before performing any maintenance on the gen-
erator, disconnect its battery cables to prevent
accidental start-up. Disconnect the cable from the
battery post indicated by a NEGATIVE, NEG or (–)
first. Reconnect that cable last.
• Never use the generator or any of its parts as a
step. Stepping on the unit can stress and break
parts, and may result in dangerous operating con-
ditions from leaking exhaust gases, fuel leakage,
oil leakage, etc.
ELECTRICAL HAZARDS
• All Stationary Emergency Generators covered by
this manual produce dangerous electrical voltages
and can cause fatal electrical shock. Utility power
delivers extremely high and dangerous voltages
to the transfer switch as well as the generator.
Avoid contact with bare wires, terminals, connec-
tions, etc., on the generator as well as the transfer
switch, if applicable. Ensure all appropriate cov-
ers, guards and barriers are in place before operat-
ing the generator. If work must be done around an
operating unit, stand on an insulated, dry surface
to reduce shock hazard.
Do not handle any kind of electrical device while
standing in water, while barefoot, or while hands or
feet are wet. DANGEROUS ELECTRICAL SHOCK
MAY RESULT.
If personnel must stand on metal or concrete while
installing, operating, servicing, adjusting or repair-
ing this equipment, place insulative mats over a
dry wooden platform. Work on the equipment only
while standing on such insulative mats.
• The National Electrical Code (NEC) requires the
frame and external electrically conductive parts of
the generator to be connected to an approved earth
ground. This grounding will help prevent danger-
ous electrical shock that might be caused by a
ground fault condition in the generator or by static
electricity. Never disconnect the ground wire.
Wire gauge sizes of electrical wiring, cables and
cord sets must be adequate to handle the maxi-
mum electrical current (ampacity) to which they
will be subjected.
Before installing or servicing this (and related)
equipment, make sure that all power voltage
supplies are positively turned off at their source.
Failure to do so will result in hazardous and pos-
sibly fatal electrical shock.
• Connecting this unit to an electrical system nor-
mally supplied by an electric utility shall be by
means of a transfer switch so as to isolate the
generator electric system from the electric utility
distribution system when the generator is operat-
ing. Failure to isolate the two electric system power
sources from each other by such means will result
in damage to the generator and may also result
in injury or death to utility power workers due to
backfeed of electrical energy.
Stationary Emergency Generators installed with
an automatic transfer switch will crank and start
automatically when normal (utility) source volt-
age is removed or is below an acceptable preset
level. To prevent such automatic start-up and pos-
sible injury to personnel, disable the generator’s
automatic start circuit (battery cables, etc.) before
working on or around the unit. Then, place a “Do
Not Operate” tag on the generator control panel
and on the transfer switch.
In case of accident caused by electric shock, imme-
diately shut down the source of electrical power.
If this is not possible, attempt to free the victim
from the live conductor. AVOID DIRECT CONTACT
WITH THE VICTIM. Use a nonconducting imple-
ment, such as a dry rope or board, to free the vic-
tim from the live conductor. If the victim is uncon-
scious, apply first aid and get immediate medical
help.
• Never wear jewelry when working on this equip-
ment. Jewelry can conduct electricity resulting in
electric shock, or may get caught in moving com-
ponents causing injury.
FIRE HAZARDS
Keep a fire extinguisher near the generator at all
times. Do NOT use any carbon tetra-chloride type
extinguisher. Its fumes are toxic, and the liquid
can deteriorate wiring insulation. Keep the extin-
guisher properly charged and be familiar with its
use. If there are any questions pertaining to fire
extinguishers, consult the local fire department.
EXPLOSION HAZARDS
• Properly ventilate any room or building housing
the generator to prevent build-up of explosive gas.
Do not smoke around the generator. Wipe up any
fuel or oil spills immediately. Ensure that no com-
bustible materials are left in the generator com-
partment, or on or near the generator, as FIRE or
EXPLOSION may result. Keep the area surround-
ing the generator clean and free from debris.
These generators may operate using one of sev-
eral types of fuels. All fuel types are potentially
FLAMMABLE and/or EXPLOSIVE and should be
handled with care. Comply with all laws regulat-
ing the storage and handling of fuels. Inspect the
unit’s fuel system frequently and correct any leaks
immediately. Fuel supply lines must be prop-
erly installed, purged and leak tested according to
applicable fuel-gas codes before placing this equip-
ment into service.
Diesel fuels are highly FLAMMABLE. Gaseous
fluids such as natural gas and liquid propane
(LP) gas are extremely EXPLOSIVE. Natural gas
is lighter than air, and LP gas is heavier than air;
install leak detectors accordingly.
1-3
Stationary Emergency Generator
Important Safety Instructions
Safety 001 Rev. B 10/08
Download manual in English (PDF, 16 MB)
(Consider the environment and only print this manual if it is really necessary)

Loading…

Rating

Let us know what you think about the Generac QT08054KNANA Generator by leaving a product rating. Want to share your experiences with this product or ask a question? Please leave a comment at the bottom of the page.
Are you satisfied with the Generac QT08054KNANA Generator?
Yes No
Be the first to rate this product
0 votes

Join the conversation about this product

Here you can share what you think about the Generac QT08054KNANA Generator. If you have a question, first carefully read the manual. Requesting a manual can be done by using our contact form.

More about this manual

We understand that it’s nice to have a paper manual for your Generac QT08054KNANA Generator. You can always download the manual from our website and print it yourself. If you would like to have an original manual, we recommend you contact Generac. They might be able to provide an original manual. Are you looking for the manual of your Generac QT08054KNANA Generator in a different language? Choose your preferred language on our homepage and search for the model number to see if we have it available.

Specifications

Brand Generac
Model QT08054KNANA
Category Generator
File type PDF
File size 16 MB

All manuals for Generac Generator
More manuals of Generator

Manual Generac QT08054KNANA Generator

Related products

Related categories