9)Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks
and component inspection procedures. If a fault exists that could compromise safety,
then no electrical supply shall be connected to the circuit until it is satisfactorily dealt
with. If the fault cannot be corrected immediately but it is necessary to continue
operation, an adequate temporary solution shall be used. This shall be reported to
the owner of the equipment so all parties are advised.
Initial safety checks shall include:
That capacitors are discharged: this shall be done in a safe manner to avoid
possibility of sparking; That there no live electrical components and wiring are
exposed while charging, recovering or purging the system; That there is continuity
of earth bonding.
7.Repairs to sealed components
1)During repairs to sealed components, all electrical supplies shall be disconnected
from the equipment
being worked upon prior to any removal of sealed covers, etc. If it is absolutely
necessary to have an electrical supply to equipment during servicing, then a
permanently operating form of leak detection shall be located at the most critical
point to warn of a potentially hazardous situation.
2)Particular attention shall be paid to the following to ensure that by working on
electrical components, the casing is not altered in such a way that the level of
protection is aected. This shall include damage to cables, excessive number of
connections, terminals not made to original specification, damage to seals, incorrect
fitting of glands, etc. Ensure that apparatus is mounted securely. Ensure that seals or
sealing materials have not degraded such that they no longer serve the purpose of
preventing the ingress of flammable atmospheres. Replacement parts shall be in
accordance with the manufacturer's specifications.
NOTE: The use of silicon sealant may inhibit the eectiveness of some types of leak
detection equipment. Intrinsically safe components do not have to be isolated prior
to working on them.
Do not apply any permanent inductive or capacitance loads to the circuit without
ensuring that this will not exceed the permissible voltage and current permitted for
the equipment in use. Intrinsically safe components are the only types that can be
worked on while live in the presence of a flammable atmosphere. The test apparatus
shall be at the correct rating. Replace components only with parts specified by the
manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere
from a leak.
8.Repair to intrinsically safe components
7)Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking
into the system or conducting any hot work. A degree of ventilation shall continue
during the period that the work is carried out. The ventilation should safely disperse
any released refrigerant and preferably expel it externally into the atmosphere.
8)Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose
and to the correct specification. At all times the manufacturer's maintenance and
service guidelines shall be followed. If in doubt consult the manufacturer's technical
department for assistance. The following checks shall be applied to installations
using flammable refrigerants: The charge size is in accordance with the room size
within which the refrigerant containing parts are installed;
The ventilation machinery and outlets are operating adequately and are not
obstructed; If an indirect refrigerating circuit is being used, the secondary circuit
shall be checked for the presence of refrigerant; Marking to the equipment continues
to be visible and legible. Markings and signs that are illegible shall be corrected;
Refrigeration pipe or components are installed in a position where they are unlikely
to be exposed to any substance which may corrode refrigerant containing
components, unless the components are constructed of materials which are
inherently resistant to being corroded or are suitably protected against being so
corroded.
flammable refrigerant can possibly be released to the surrounding space. Prior to work
taking place, the area around the equipment is to be surveyed to make sure that there
are no flammable hazards or ignition risks. No Smoking signs shall be displayed.
Download manual in English (PDF, 32.71 MB)
(Consider the environment and only print this manual if it is really necessary)

Loading…

Rating

Let us know what you think about the Comfee CDDOE-12DEN7-QA3-(EU) Dehumidifier by leaving a product rating. Want to share your experiences with this product or ask a question? Please leave a comment at the bottom of the page.
Are you satisfied with the Comfee CDDOE-12DEN7-QA3-(EU) Dehumidifier?
Yes No
Be the first to rate this product
0 votes

Join the conversation about this product

Here you can share what you think about the Comfee CDDOE-12DEN7-QA3-(EU) Dehumidifier. If you have a question, first carefully read the manual. Requesting a manual can be done by using our contact form.

More about this manual

We understand that it’s nice to have a paper manual for your Comfee CDDOE-12DEN7-QA3-(EU) Dehumidifier. You can always download the manual from our website and print it yourself. If you would like to have an original manual, we recommend you contact Comfee. They might be able to provide an original manual. Are you looking for the manual of your Comfee CDDOE-12DEN7-QA3-(EU) Dehumidifier in a different language? Choose your preferred language on our homepage and search for the model number to see if we have it available.

Specifications

Brand Comfee
Model CDDOE-12DEN7-QA3-(EU)
Category Dehumidifiers
File type PDF
File size 32.71 MB

All manuals for Comfee Dehumidifiers
More manuals of Dehumidifiers

Frequently Asked Questions about Comfee CDDOE-12DEN7-QA3-(EU) Dehumidifier

Our support team searches for useful product information and answers to frequently asked questions. If you find an inaccuracy in our frequently asked questions, please let us know by using our contact form.

Can I turn on my dehumidifier immediately after purchase? Verified

No, just like a refrigerator or freezer the device should be standing upright for at least 2 hours, but preferrably 24 hours before turning it on for the first time.

This was helpful (801) Read more

What is the ideal humidity for a living space? Verified

The ideal humidity in a house is between 40-60%. At a higher or lower humidity, fungi, bacteria and viruses are more likely to develop and you can experience personal discomfort.

This was helpful (618) Read more

How can I correctly transport my dehumidifier? Verified

Dehumidifiers should always be transported in an upright position and well protected. Any other way of transport might cause damage to the device.

This was helpful (531) Read more