CM67Z ZONE CONTROLLER
3
EN0R 8534R0 03/03
INSTALLER SET-UP
This feature allows you to adjust CM67
Z
to match the specific requirements of the application. Installer Set-up allows to:
Set-up specific applications parameters
Enable special features
Configure zoning system operation
Special Features Description Setting
Optimisation -
Adaptive Intelligent
Recovery
TM
1:OP
The CM67
Z
will adjust the start time at upward setpoint changes so the
desired temperature is reached at the programmed time e.g 7:00 temperature
21
o
C.The chronotherm will monitor the start-up period and use this
information to modify the start time calculation for the next upward setpoint
change. The system will restrict the start time to a max of 3 hours before the
programmed comfort time
0* – disabled
1 – enabled
Minimum boiler On
time
2:Ot
Defines the minimum switch on and off time for the boiler. The selected value
is transferred via RF communication to HC60NG and is used as the key
boiler control parameter
1 min
(other values: 2, 3, 4,
5)
AM-PM/ 24hr
Display
3:Cl
Change display format (default 24hr) 0* – 24 hr display
1 – AM/PM display
Internal temperature
sensor
7:tS
Allows configuring of the CM67
Z
to use its own build in sensor to measure the
temperature in zone1. The measured values is used by all HR80 is zone1.
When built-in sensor is disabled will also display the measured temperature.
0* - disabled
1 – enabled
Cycle rate
9:Cr
Determines the length of boiler cycle. The selected value is transferred via
RF communication to HC60NG and is used as the key boiler control
parameter
6 cph (10 min)*
(other values: 3, 9)
System Timing
Master
10:St
To ensure synchronous operation of the boiler and zone valves (controlled by
HC60NG) in the system one of the CM67
Z
has to be configured as the
system timing master sending the sync signal co-ordinating on/off cycling of
all HC60NGs.
0* – normal operation
1 – system timing
master
Fail-safe mode
16:LC
The CM67
Z
allows you to set the fail-safe mode of operation of the heating
system if radio communication is lost. By default HC60 boiler controller relay
will be switched OFF in case of communication loss. Alternatively you may
choose to cycle the boiler at 2 min ON and 8min OFF. Useful when the
building is not occupied for long periods of time and there is a high risk of
frost damage.
0* – relay OFF
1 – relay cycles
Zone valve control
enable
17:CE
Allows sending a special message to control HC60NG operating as zone
valve controller. In this way flow in the whole zone can be controlled with just
one valve. This type of control can only be used for zone 1
0* - disabled
1 – enabled
Open window
detection function
18:Ho
According to factory default operation HR80 controller will close the valve
when open window is detected. This parameter allows configuring the HR80
to perform or ignore this function.
3* - enabled
0 - disabled in zone 1
& 2
1 - enabled in zone 1
2 – enabled in zone 2
HR80 local override
19:HL
According to factory default local override of HR80 setpoint is enabled. This
parameter allows disabling this function if required.
3* - enabled
0 - disabled in zone 1
& 2
1 - enabled in zone 1
2 – enabled in zone 2
* - factory default values
Download manual in English (PDF, 0.65 MB)
(Consider the environment and only print this manual if it is really necessary)

Loading…

Rating

Let us know what you think about the Honeywell CM67z Thermostat by leaving a product rating. Want to share your experiences with this product or ask a question? Please leave a comment at the bottom of the page.
Are you satisfied with the Honeywell CM67z Thermostat?
Yes No
Be the first to rate this product
0 votes

Join the conversation about this product

Here you can share what you think about the Honeywell CM67z Thermostat. If you have a question, first carefully read the manual. Requesting a manual can be done by using our contact form.

More about this manual

We understand that it’s nice to have a paper manual for your Honeywell CM67z Thermostat. You can always download the manual from our website and print it yourself. If you would like to have an original manual, we recommend you contact Honeywell. They might be able to provide an original manual. Are you looking for the manual of your Honeywell CM67z Thermostat in a different language? Choose your preferred language on our homepage and search for the model number to see if we have it available.

Specifications

Brand Honeywell
Model CM67z
Category Thermostats
File type PDF
File size 0.65 MB

All manuals for Honeywell Thermostats
More manuals of Thermostats

Frequently Asked Questions about Honeywell CM67z Thermostat

Our support team searches for useful product information and answers to frequently asked questions. If you find an inaccuracy in our frequently asked questions, please let us know by using our contact form.

What is the dead zone of a thermostat? Verified

Many modern thermostats have a dead zone. If the temperature deviates less than 4°C from the set temperature, the system will not heat or cool. This so called dead zone of the thermostat prevents the system from turning on and off too often, saving energy.

This was helpful (1593) Read more

What is the best place to mount a thermostat? Verified

The best place for a thermostat is approximately 1,5 meter above the ground. Never place the thermostat nead a radiator or other heat emitting equipment or in direct sunlight. Choose a room that is used often. In most cases this is the living room.

This was helpful (996) Read more