FUEL SYSTEM
FUEL REQUIREMENTS
The Stationary Emergency Generator may be equipped
with one of the following fuel systems:
Natural gas fuel system
Propane vapor (PV) fuel system
Liquid propane (LP) fuel system
The Manual Drawing Listing that is affixed to the
unit includes the “Identification Code,” which may be
used to identify the type of fuel system installed on
the unit.
Recommended fuels should have a Btu content of at
least 1,000 Btu's per cubic foot for natural gas; or at
least 2,520 Btu's per cubic foot for LP gas. Ask the
fuel supplier for the Btu content of the fuel.
Required fuel pressure for natural gas is 11 inches
to 14 inches water column (0.4 to 0.5 psi); and for
liquid propane, 11 inches to 14 inches of water
column (0.4 to 0.5 psi).
NOTE:
Any piping used to connect the generator to the
fuel supply should be of adequate size to ensure
the fuel pressure NEVER drops below 11 inches
water column for natural gas or 11 inches water
column for liquid propane for all load ranges.
NOTE:
It is the responsibility of the installer to make sure
that only the correct recommended fuel is sup-
plied to the generator fuel system. Thereafter, the
owner/operator must make certain that only the
proper fuel is supplied.
NATURAL GAS FUEL SYSTEM
Natural gas is supplied in its vapor state. In most
cases, the gas distribution company provides piping
from the main gas distribution line to the standby
generator site. The following information applies to
natural gas fuel systems.
Gas pressure in a building is usually regulated by
national, state and local codes.
To reduce gas pressure to a safe level before
the gas enters a building, a primary regulator is
needed. The natural gas supplier may or may not
supply such a regulator.
It is the responsibility of the gas supplier to make
sure sufficient gas pressure is available to operate
the primary regulator.
Gas pressure at the inlet to the fuel shutoff sole-
noid should not exceed approximately 14 inches
water column (0.5 psi). Optimum pressure at the
fuel shutoff solenoid is 11 inches water column
(0.4 psi).
PROPANE VAPOR WITHDRAWAL FUEL SYSTEM
This type of system utilizes the vapors formed above
the liquid fuel in the supply tank. Approximately 10
to 20 percent of the tank capacity is needed for fuel
expansion from the liquid to the vapor state. The
vapor withdrawal system is generally best suited for
smaller engines that require less fuel. The installer
should be aware of the following:
The natural gas and LP gas systems are similar.
However, the natural gas system delivers gas at a
pressure of approximately five inches water col-
umn to the carburetor.
When ambient temperatures are low and engine
fuel consumption is high, the vapor withdrawal
system may not function efficiently.
Ambient temperatures around the supply tank
must be high enough to sustain adequate vaporiza-
tion, or the system will not deliver the needed fuel
volume.
In addition to the cooling effects of ambient air, the
vaporization process itself provides an additional
cooling effect.
LP FUEL SYSTEM
LP is supplied as a liquid in pressure tanks. It is
usually made up of propane, butane, or a mixture of
the two gases. Propane tends to vaporize readily even
at temperatures as low as -20° F (-29° C). However,
butane reverts to its liquid state when temperatures
drop below 32° F (0° C).
LP in a liquid withdrawal system must be converted
to its gaseous state before it is introduced into the
engine carburetor. A vaporizer-converter is generally
used to accomplish this. In such a converter, heated
engine coolant is ported through the converter to
provide the necessary heat for conversion of the fuel
from a liquid to a gaseous state.
5-1
Stationary Emergency Generator
Fuel Systems
FuelSys002 Rev. B 10/08
Download manual in English (PDF, 16 MB)
(Consider the environment and only print this manual if it is really necessary)

Loading…

Rating

Let us know what you think about the Generac QT08054KNANA Generator by leaving a product rating. Want to share your experiences with this product or ask a question? Please leave a comment at the bottom of the page.
Are you satisfied with the Generac QT08054KNANA Generator?
Yes No
Be the first to rate this product
0 votes

Join the conversation about this product

Here you can share what you think about the Generac QT08054KNANA Generator. If you have a question, first carefully read the manual. Requesting a manual can be done by using our contact form.

More about this manual

We understand that it’s nice to have a paper manual for your Generac QT08054KNANA Generator. You can always download the manual from our website and print it yourself. If you would like to have an original manual, we recommend you contact Generac. They might be able to provide an original manual. Are you looking for the manual of your Generac QT08054KNANA Generator in a different language? Choose your preferred language on our homepage and search for the model number to see if we have it available.

Specifications

Brand Generac
Model QT08054KNANA
Category Generator
File type PDF
File size 16 MB

All manuals for Generac Generator
More manuals of Generator

Manual Generac QT08054KNANA Generator

Related products

Related categories