MAINTENANCE PERFORMED BY
AUTHORIZED SERVICE DEALERS
Before working on the Stationary Emergency
Generator, ensure the following:
The AUTO/OFF/MANUAL switch is in the OFF position.
The 15A fuse has been removed from the control box.
The 120VAC supply to the battery charger is switched OFF.
The negative battery cable has been removed.
EVERY THREE MONTHS
1. Check battery state of charge and condition.
2. Inspect and test fuel system.
3. Check transfer switch.
4. Inspect exhaust system.
5. Check engine ignition system.
6. Check fan belts.
ONCE EVERY SIX MONTHS
1. Test Engine Safety Devices (low oil pressure, low coolant
level, high coolant temperature).
ONCE ANNUALLY
1. Test engine governor. Adjust or repair, if needed.
2. Clean, inspect generator.
3. Flush cooling system.
4. Clean/re-gap spark plugs or replace as necessary.
FIRST 30 OPERATING HOURS
1. Change engine "break-in" oil and oil filter.
FIRST 100 OPERATING HOURS
1. Change engine oil and oil filter. (After initial change, service
engine oil and filter at 150 operating hours or 6 months,
whichever comes first.)
EVERY 500 OPERATING HOURS
1. Service air cleaner.
2. Check starter.
3. Check engine DC alternator.
COOLING SYSTEM
Air intake and outlet openings in the generator compartment must
be open and unobstructed for continued proper operation. This
includes such obstructions as high grass, weeds, brush, leaves
and snow.
Without sufficient cooling and ventilating air flow, the engine/gen-
erator quickly overheats, which causes it to shut down.
The exhaust system parts from this product get
extremely hot and remain hot after shutdown.
High grass, weeds, brush, leaves, etc. must
remain clear of the exhaust. Such materials may
ignite and burn from the heat of the exhaust
system.
CHECKING FLUID LEVELS
CHECK ENGINE OIL
Check engine crankcase oil level (Figure 10.1) at least every 20
hours of operation, or prior to use.
Remove oil dipstick and wipe dry with a clean, lint-free cloth.
Install oil dipstick, then remove again.
Oil should be between FULL and ADD marks.
If oil level is below the dipstick ADD mark, remove oil fill cap.
Add the recommended oil to bring oil level up to the FULL
mark. DO NOT FILL ABOVE THE “FULL” MARK. See “Engine Oil
Recommendations” for recommended oils.
Figure 10.1 - Oil Dipstick and Oil Fill Cap
Oil Fill
Oil
Dipstic
k
Oil Filter
BATTERY FLUID
Check battery electrolyte fluid at least once weekly. Fluid should
cover separators in all battery cells. If fluid level is low, add distilled
water to cover tops of separators. DO NOT USE TAP WATER IN
BATTERY.
10-1
Stationary Emergency Generator
Maintenance
Maint013 Rev. D 04/09
Download manual in English (PDF, 16 MB)
(Consider the environment and only print this manual if it is really necessary)

Loading…

Rating

Let us know what you think about the Generac QT08054KNANA Generator by leaving a product rating. Want to share your experiences with this product or ask a question? Please leave a comment at the bottom of the page.
Are you satisfied with the Generac QT08054KNANA Generator?
Yes No
Be the first to rate this product
0 votes

Join the conversation about this product

Here you can share what you think about the Generac QT08054KNANA Generator. If you have a question, first carefully read the manual. Requesting a manual can be done by using our contact form.

More about this manual

We understand that it’s nice to have a paper manual for your Generac QT08054KNANA Generator. You can always download the manual from our website and print it yourself. If you would like to have an original manual, we recommend you contact Generac. They might be able to provide an original manual. Are you looking for the manual of your Generac QT08054KNANA Generator in a different language? Choose your preferred language on our homepage and search for the model number to see if we have it available.

Specifications

Brand Generac
Model QT08054KNANA
Category Generator
File type PDF
File size 16 MB

All manuals for Generac Generator
More manuals of Generator

Manual Generac QT08054KNANA Generator

Related products

Related categories