Leak detection methods
The following leak detection methods are deemed acceptable for systems containing flammable
refrigerants:
Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be
adequate or may need recalibration. Detection equipment shall be calibrated in a refrigerant-free area.
Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used.
Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be
calibrated to the refrigerant employed and the appropriate percentage of gas (25% maximum) is
confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing
chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper or
pipe-work.
If a leak is suspected, all naked flames shall be removed or extinguished.
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered
from the system or isolated by means of shut off valves in a part of the system remote from the leak.
Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the
brazing process.
Removal and evacuation
When breaking into the refrigerant circuit to make repairs or for any other purpose conventional
procedures shall be used. However, it is important that the best practice is followed since flammability is a
consideration. The following procedures shall be adhered to:
Safely remove refrigerant following local and national regulations;
Evacuate;
Purge the circuit with inert gas (optional for A2L);
Evacuate (optional for A2L);
Continuously flush or purge with inert gas when using flame to open circuit; and
Open the circuit
The refrigerant charge shall be recovered into the correct recovery cylinders if venting is not allowed by
local and national codes. For appliances containing flammable refrigerants, the system shall be purged
with oxygen-free non-flammable refrigerants. This process might need to be repeated several times.
Compressed air or oxygen shall not be used for purging refrigerant systems.
For appliances containing flammable refrigerants, refrigerants purging shall be achieved by breaking
the vacuum in the system with oxygen-free nitrogen and continuing to fill until the working pressure is
achieved, then venting to atmosphere, and finally pulling down to a vacuum (optional for A2L). This
process shall be repeated until no refrigerant is within the system (optional for A2L). When the final
oxygen-free nitrogen charge is used, the system shall be vented down to atmospheric pressure to enable
work to take place.
The outlet for the vacuum pump shall not be close to any potential ignition sources, and ventilation shall be
available.
SAVE THESE INSTRUCTIONS!
Important Safety Information
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
Download manual in English (PDF, 3.4 MB)
(Consider the environment and only print this manual if it is really necessary)

Loading…

Rating

Let us know what you think about the Danby DAC080EBIBDB Air Conditioner by leaving a product rating. Want to share your experiences with this product or ask a question? Please leave a comment at the bottom of the page.
Are you satisfied with the Danby DAC080EBIBDB Air Conditioner?
Yes No
Be the first to rate this product
0 votes

Join the conversation about this product

Here you can share what you think about the Danby DAC080EBIBDB Air Conditioner. If you have a question, first carefully read the manual. Requesting a manual can be done by using our contact form.

More about this manual

We understand that it’s nice to have a paper manual for your Danby DAC080EBIBDB Air Conditioner. You can always download the manual from our website and print it yourself. If you would like to have an original manual, we recommend you contact Danby. They might be able to provide an original manual. Are you looking for the manual of your Danby DAC080EBIBDB Air Conditioner in a different language? Choose your preferred language on our homepage and search for the model number to see if we have it available.

Specifications

Brand Danby
Model DAC080EBIBDB
Category Air Conditioners
File type PDF
File size 3.4 MB

All manuals for Danby Air Conditioners
More manuals of Air Conditioners

Frequently Asked Questions about Danby DAC080EBIBDB Air Conditioner

Our support team searches for useful product information and answers to frequently asked questions. If you find an inaccuracy in our frequently asked questions, please let us know by using our contact form.

How often should I clean or replace the filters in my air conditioner? Verified

It's advisable to check the filters of your air conditioner 4 times a year. Dirty filters can be cleaned with the use of a vacuum cleaner or can be washed, depending on which type they are. During maintenance a professional should judge whether it is time to replace the filters.

This was helpful (2746) Read more

What does BTU stand for? Verified

BTU stands for British Thermal Unit. This is unit to indicate the capacity to cool.

This was helpful (986) Read more

Does every air conditioner also function as a dehumidifier? Verified

The cold air produced by an air conditioner often has a relatively low humidity. However, the effect is less than when using an actual dehumidifier. Some air conditioners do have a special feature to dehumidify the air.

This was helpful (752) Read more

What is R-410A? Verified

R-410A is a cooling agent that is used in appliances that cool up to 0°C, like refrigerators and air conditioners. It is the replacement of older cooling agents and does not damage the ozon layer.

This was helpful (517) Read more

Does an air conditioner have a negative influence on air quality? Verified

If the air conditioner has been properly maintained then it will have no influence on air quality. If for example a filter hasn't been replaced for a long time, or other maintenance has not been performed, than an air conditioner can produce dirty air.

This was helpful (372) Read more

What is the best place to mount the indoor unit of a split-type air conditioner? Verified

This depends on the space, but in general the following rules can be followed. Make sure that there is nothing obstructing the airflow. Make sure the location is accessible for maintenance. Mount the unit at least 2 meters from the ground.

This was helpful (370) Read more

Can I place my mobile air conditioner in a cabinet to get it out of sight? Verified

No, absolutely not. A mobile air conditioner needs space to allow airflow and air intake. In a small space the device can overheat.

This was helpful (369) Read more