INSTALLATION INSTRUCTIONS
BRITON 996 FIG.1
ELECTRO MAGNETIC HOLD OPEN/FREE SWING DOOR CLOSER
24VDC
SURFACE FIXED TO ‘PULL’ (HINGE) SIDE OF DOOR.
SIZE 3 closer suitable for doors up to 950mm wide and 60kg in weight
SIZE 4 closer suitable for doors up to 1100mm wide and 80kg in weight
SIZE 5 closer suitable for doors up to 1250mm wide and 100kg in weight
This closer unit incorporates an electro magnet which is normally interfaced with a detector/alarm system.
In an emergency or a power failure, the electro magnet when de-energised will cause the closer to close the
door into its frame. A 13mm A/F spanner is required
to carry out adjustments to arm set or convert from hold
open to free swing function.
Hold open function enables unit to hold door open until automatically released or pulled closed manually.
Angle of hold can be adjusted from 85° to 95° approx. and 103° to 110° approx.
Free Swing function
setting allows door to be independent of closer control. When unit is automatically
released the door will be driven closed from whatever position it may have been left open. Adjustment of
catch plate provides for a free swing variance of 85° to 95° approx. Door can open to approx. 110° max.
subject to hinge projection and surrounding structure.
Warning: When Briton 996 is used in the free swing mode the door is not under the control of the damping
action and will slam in windy or draughty conditions.
THIS CLOSER UNIT IS EASILY CONVERTED TO SUIT EITHER HAND OF DOOR, for conversion
instructions see diagram 4.
IMPORTANT
Door must swing freely and close firm into its rebate to enable the closer to operate efficiently. This is
particularly important for fire/smoke doors and we recommend that doors be hung on ball bearing butt hinges
to BS EN 1935 and that latches and smoke seals be of a type that offer minimum resitance to closing.
Failure to address these requirements may result in an ineffective fire/smoke door installation.
DOOR STOP MUST BE FITTED TO PREVENT DOOR FROM OPENING JUST
BEYOND SETANGLE OF
HOLD OPEN OR FREE SWING SETTING.
Under no circumstances should the door closer be dismantled.
ELECTRICAL INFORMATION
SPECIFICATION Electro-magnet continuous rating: 2.35 watts max at 26v DC.
Power Requirements: 24v DC - 90 mA nominal.
TESTING Check that voltage is within specified range at each unit after installation.
It is recommended that the equipment is tested at weekly intervals for correct function.
NOTE: Power for ancillary devices must not be drawn from the alarm system except under alarm
conditions and then must not reduce the reliability of the supply. (BS.5839 Pt. 1).
TYPICAL WIRING DIAGRAM
NOTE: Power supply feed to electro magnet is through flexible armoured loop.
IMPORTANT
This closer should be installed by a competent fixer who must pass these instructions onto the site or
maintenance manager once the closer unit has been satisfactorily fixed, wired and tested.
No Responsibility can be accepted by the manufacturers if these installation instructions are disregarded.
Diagram 1
24v DC output
240v AC
50Hz input
Briton 996 units
NC
+
+
-
++
---
P.R. relay controlled by alarm
Unit is polarised indicated by the
red (+VE) and black (-VE) wires.
Transformer
rectifier unit
(F.S.R.)
0996/091/00
Issue 01
Download manual in English (PDF, 0.57 MB)
(Consider the environment and only print this manual if it is really necessary)

Loading…

Rating

Let us know what you think about the Briton 996 Door Closer by leaving a product rating. Want to share your experiences with this product or ask a question? Please leave a comment at the bottom of the page.
Are you satisfied with the Briton 996 Door Closer?
Yes No
0%
100%
1 vote

Join the conversation about this product

Here you can share what you think about the Briton 996 Door Closer. If you have a question, first carefully read the manual. Requesting a manual can be done by using our contact form.

Rob Hornsey 22-11-2021
Door closer 996 will not stay open when pushed back

reply | This was helpful (0)

More about this manual

We understand that it’s nice to have a paper manual for your Briton 996 Door Closer. You can always download the manual from our website and print it yourself. If you would like to have an original manual, we recommend you contact Briton. They might be able to provide an original manual. Are you looking for the manual of your Briton 996 Door Closer in a different language? Choose your preferred language on our homepage and search for the model number to see if we have it available.

Specifications

Brand Briton
Model 996
Category Door Closers
File type PDF
File size 0.57 MB

All manuals for Briton Door Closers
More manuals of Door Closers

Frequently Asked Questions about Briton 996 Door Closer

Our support team searches for useful product information and answers to frequently asked questions. If you find an inaccuracy in our frequently asked questions, please let us know by using our contact form.

The door closer squeaks when the door opens, what can I do? Verified

Most door closers can be placed directly after purchase without additional lubrication. However, after time it might be necessary to lubricate the hinges to prevent wear and avoid unwanted noises.

This was helpful (318) Read more
Manual Briton 996 Door Closer