Manual Seitron TAEKW02D Thermostat

Need a manual for your Seitron TAEKW02D Thermostat? Below you can view and download the PDF manual for free in English. This product currently has 2 frequently asked questions, 0 comments and has 0 votes. If this is not the manual you want, please contact us.

Is your product defective and the manual offers no solution? Go to a Repair Café for free repair services.

Manual

Loading…

TAEKW02D 011602A2 240605
Via Prosdocimo, 30
I-36061 BASSANO DEL GRAPPA (VI)
Tel.: +39.0424.567842
Fax.: +39.0424.567849
http://www.seitron.it
TAE KW0 2D
REGOLATORE PROPORZIONALE-INTEGRALE
Alimentazione 24V~/=
Regolazione proporzionale-integrale
Tensione di uscita 0 .. 10V
Riduzione notturna
Tempo di integrazione selezionabile
Banda proporzionale regolabile
PROPORTIONAL-INTEGRAL REGULATOR
24V~/= power supply
Proportional-integral regulation
0 .. 10V voltage output
Night reduction facility
Selectable integration time
Adjustable proportional band
Fig. 2: Tempo di integrazione e trimmer banda proporzionale / Integration time and proportional band trimmer
A B C D
Selezione del tempo di
integrazione
A: 3 min. (regolazione in fabbrica)
B: 9 min.
C: 18 min.
D: 27 min.
Integration time selection
A: 3 min. (factory set)
B: 9 min.
C: 18 min.
D: 27 min.
J1
Trimmer banda proporzionale
Proportional band trimmer
5°
10°
15°
20°
25°
30°
Foro di fissaggio
Fixing screw hole
Fig. 1: Aspetto esteriore TAEKW02D /
TEAKW02D Aspect exterior
Fig. 2: Schema di collegamento TAEKW02D / TEAKW02D wiring diagram
Riduzione notturna
Night reduction
Uscita
Output
0 .. 10V=
Sonda esterna
External
probe
TAEKW02D 011602B2 240605
FUNZIONAMENTO
TAE KW0 2D (Fig. 1) è un regolatore proporzionale - integrale per
l’acqua di mandata. La tensione di uscita (0 .. 10V) si ottiene
mediante la somma della parte proporzionale e della parte
integrale. La parte proporzionale si ottiene come dimostrato nel
seguente grafico:
Quando la temperatura raggiunge il valore del set point, la
tensione di uscita è pari a 5 V e diminuisce all’aumentare della
temperatura. La banda proporzionale è regolabile mediante il
trimmer interno da 1°C a 30°C (vedi figura 3). La parte integrale è
dipendente dal tempo: quando l’errore tra la temperatura e il set
point è fisso, esso raggiunge il valore della parte proporzionale in
un intervallo di tempo uguale al tempo di integrazione. Il tempo di
integrazione è selezionabile regolando il jumper J1 (vedi figura 3).
SCHEMA DI COLLEGAMENTO (Fig. 2)
Una riduzione notturna fissa di 4° si ottiene collegando un
interruttore esterno ai terminali 7 e 8 (la riduzione è attiva quando
l’interruttore è chiuso). Diversi regolatori possono essere collegati
in parallelo allo stesso interruttore di riduzione notturna (per
funzionamento centralizzato), ma la polarità dei collegamenti deve
essere rigorosamente rispettata.
CARATTERISTICHE TECNICHE
Alimentazione: 24V~/=, ±10%, 50Hz
Potenza assorbita: 0.7VA
Range di regolazione:
Set point: 20°C .. 70°C
Banda proporzionale: 1°C .. 30°C
Riduzione notturna: 4°C
Tempo di integrazione: 3, 9, 18, 27 minuti
Tipo di sensore: Esterno, STLPTSA150
PTC 2026 Ohm @25°C
Precisione: ±1°C.
Risoluzione: ±2.5°C
Uscita: Tensione di uscita (0 .. 10V=)
Max corrente di uscita: 10mA
Grado di protezione: IP 30
Temp. di funzionamento: 0°C .. 40°C
Temp. di stoccaggio: -10°C .. +50°C
Limite di umidità: 10% .. 80% RH non condensante
Dimensioni: 85 x 85 x 31 mm (L x A x P)
Peso: ~ 205 gr.
a ATTENZIONE
- Per i collegamenti della sonda usare cavi di sezione minima
1,5 mm² e di lunghezza massima di 25 m. Non passare i cavi
della sonda nelle canaline della rete.
- Collegare l'apparecchio alla rete di alimentazione tramite un
interruttore onnipolare conforme alle norme vigenti e con
distanza di apertura dei contatti di almeno 3 mm in ciascun
polo.
- L'installazione ed il collegamento elettrico del dispositivo
devono essere eseguiti da personale qualificato ed in
conformità alle leggi vigenti.
- Prima di effettuare qualsiasi collegamento accertarsi che la
rete elettrica sia scollegata.
Nell'ottica di un continuo sviluppo dei propri prodotti, il costruttore si riserva il
diritto di apportare modifiche a dati tecnici e prestazioni senza preavviso.
Il consumatore è garantito contro i difetti di conformità del prodotto secondo la
Direttiva Europea 1999/44/c nonché il documento sulla politica di garanzia del
costruttore. Su richiesta è disponibile presso il venditore il testo completo della
garanzia.
OPERATING
TAEKW02D (Fig. 1) is a proportional-integral regulator for supply
water pipes. The output voltage (0 .. 10V) is obtained through. the
sum of a proportional part and an integral part.
The proportional part is obtained as shown in the graphic below.
When the temperature equals the set point, the output voltage is
5V and decrease if the temperature is greater. The proportional
band is adjustable through an internal trimmer from 1°C to 30°C
(Fig. 2). The integral part is time-dependant: when the error
between the temperature and the set point is fixed, it reaches the
value of the proportional part in a time interval wich equals the
integration time. The integration time is selectable by setting the
jumper J1 (Fig. 3).
WIRING DIAGRAM (Fig. 2)
A fixed 4° night reduction is obtained connecting an external
switch on terminals 7 & 8 (the reduction is active when the switch
is closed).
Several regulators can be connected in parallel to the same night
reduction external switch (for centralized operation), but the
polarity of the wires must mandatorily be respected.
TECHNICAL FEATURES
Power supply: 24V~/=, ±10%, 50Hz
Power consumption: 0.7VA
Regulation ranges:
Set point: 20°C .. 70°C
Proportional band: 1°C .. 30°C
Night reduction: 4°C
Integration time: 3, 9, 18, 27 minutes
Probe type: External, STLPTSA150
PTC 2026 Ohm @25°C
Precision: ±1°C.
Resolution: ±2.5°C
Output: Voltage output (0 .. 10V=)
Maximum output current: 10mA
Protection grade: IP 30
Operating temperature: 0°C .. 40°C
Storage temperature: -10°C .. +50°C
Humidity limits: 20% .. 80% RH non condensing
Weight: 85 x 85 x 31 mm (L X H X P)
Size: ~ 205 gr.
a WARNING
- For remote version all wirings must be made using wires
with 1,5 mm² minimum cross section and no longer than 25
m. Do not use same duct for signal wires and mains.
- The appliance must be wired to the electric mains through a
switch capable of disconnecting all poles in compliance
with the current safety standards and with a contact
separation of at least 3 mm in all poles.
- Installation and electrical wirings of this appliance must be
made by qualified technicians and in compliance with the
current standards.
- Before wiring the appliance be sure to turn the mains power
off.
In the view of a constant development of their products, the manufacturer
reserves the right for changing technical data and features without prior notice.
The consumer is guaranteed against any lack of conformity according to the
European Directive 1999/44/EC as well as to the manufacturer’s document
about the warranty policy. The full text of warranty is available on request from
the seller.
Uscita (V)
10V
5V
Temperatura
di mandata
set point
proporzionale
0V
Output (V)
10V
5V
Water
temperature
set point
proportional
0V
ITALIANO
ENGLISH
Download manual in English (PDF, 0.08 MB)
(Consider the environment and only print this manual if it is really necessary)

Loading…

Rating

Let us know what you think about the Seitron TAEKW02D Thermostat by leaving a product rating. Want to share your experiences with this product or ask a question? Please leave a comment at the bottom of the page.
Are you satisfied with the Seitron TAEKW02D Thermostat?
Yes No
Be the first to rate this product
0 votes

Join the conversation about this product

Here you can share what you think about the Seitron TAEKW02D Thermostat. If you have a question, first carefully read the manual. Requesting a manual can be done by using our contact form.

More about this manual

We understand that it’s nice to have a paper manual for your Seitron TAEKW02D Thermostat. You can always download the manual from our website and print it yourself. If you would like to have an original manual, we recommend you contact Seitron. They might be able to provide an original manual. Are you looking for the manual of your Seitron TAEKW02D Thermostat in a different language? Choose your preferred language on our homepage and search for the model number to see if we have it available.

Specifications

Brand Seitron
Model TAEKW02D
Category Thermostats
File type PDF
File size 0.08 MB

All manuals for Seitron Thermostats
More manuals of Thermostats

Frequently Asked Questions about Seitron TAEKW02D Thermostat

Our support team searches for useful product information and answers to frequently asked questions. If you find an inaccuracy in our frequently asked questions, please let us know by using our contact form.

What is the dead zone of a thermostat? Verified

Many modern thermostats have a dead zone. If the temperature deviates less than 4°C from the set temperature, the system will not heat or cool. This so called dead zone of the thermostat prevents the system from turning on and off too often, saving energy.

This was helpful (1587) Read more

What is the best place to mount a thermostat? Verified

The best place for a thermostat is approximately 1,5 meter above the ground. Never place the thermostat nead a radiator or other heat emitting equipment or in direct sunlight. Choose a room that is used often. In most cases this is the living room.

This was helpful (990) Read more